Digital 6 Zone Voice Evacuation Mixer Amplifier
SP-EV5000
Features:
▪ Digital voice evacuation system all in one amplifier.
▪ Specifications meet the standards of BS EN54-32 & EN608409.
▪ Meet UEN54-16 standards.
▪ Built-in 500W 6 zone class-D amplifier.
▪ Integration of EVAC controller, paging system, PA system & BGM system together.
▪ Built-in two separate players for EVAC and alert voice message by SD card.
▪ Built-in 6 zone AB speaker line low impedance detection.
▪ Built-in amplifier auto changeover into standby when fault.
▪ With external amplifier input to expansion the power.
▪ Capacity of connection 32 units remote microphones.
▪ Red button EVAC message push to activate with priority except fireman microphone.
▪ 6 zone speaker outputs with separate zone volume control (ATT).
▪ 6 zone separate indicator for EVAC, fault, music/paging & select.
▪ System indicators of AC, DC, fault and indicators for EVAC, alert & fireman microphone.
▪ Zone capacity of 120 zones by cascaded 19 routers.
▪ With 8 programmable control inputs and 8 programmable control outputs for voice evacuation system
▪ With Fault, EVAC outputs and Reset input for third party system integration.
▪ With fireman microphone of highest priority.
▪ Priority level: fireman mic, EVAC, input 1, remote microphone, timer & BGM.
▪ Two combo inputs for mic/line, 4 line inputs and one REC output.
▪ Two RJ45 ports for router, two RJ45 for remote microphone input and two RJ45 for LAN/WAN/Internet network.
▪ IP network module for optional to buy.
▪ AC 230V and DC24V battery input. Auto switch into the battery backup when AC fails.
Rear Panel:
Specification:
Model | SP-EV5000 |
Description | 6 Zone Voice Evacuation Amplifier |
Rated Power Output | 500W |
Fireman Microphone | 5Mv, 600Ω |
Line Inputs | Line 1-2: 385mV, 10kΩbalanced Combo. Line 3-6: 350mV, 10kΩ, RCA |
Frequency Response | 80Hz~20kHz |
THD | <1% at RMS,1KHz |
S/N Ratio | >70dB |
Speaker Output | 100V AB 8 zone speaker outputs |
REC Output | 200mV |
Control Input & Output | 8 programmable control inputs: Max 3.3V (voltage mode) or 0V closed contact. Reset control input: 0V closed contact. 8 programmable control outputs: 0V closed contact. Control output for fault & EVAC: 0V closed contact. |
Voice Message | MP3 or WMA format, two separate players of SD card with protection cover, programmable voice message up to 255, 10 years valid |
Event Record | HEX format, Hard Flash memory, events up to 1000 records, 10 years valid |
Operation Environment | Operation Temp: +5℃~+40℃. Store Temp: -20℃~+70℃. Operation Humidity: <95% |
Power Consumption | 600W |
Power Supply | AC230V or 115V & DC24V battery inputs, 50-60HZ |
AC Fuse | 250V/6.3A, slow type and restorable fuse |
Dimension/Weight | 484(W)×132(H)×449(D) mm, 24KG |
System Connection Diagram: